This product supports measurement of ground voltage and ground resistance.
The ground voltage measurement function supports both the "three-wire type" for precision measurement and the "two-wire type" for simple measurement.
You can select from the measurement ranges of x1, x10, and x100.
It has an LED to confirm the correct installation status.
It comes with a backlight (scale plate lighting) that allows you to measure in low light.
Specifications
Display: Analog meter taut band method
Used temperature and humidity: 0 to +40℃, 85%RH or less (however, no condensation)
Storage temperature and humidity: -20 to +60℃, 75%RH or less (however, no condensation)
Response time: Within 1 second
Insulation resistance: 100MΩ/DC1000V between measurement terminal and outer case
Withstand voltage: AC3700V (50/60Hz) for 1 minute between measurement terminal and outer case
Measurable ground type: 3-wire system grounding resistance measurement: From A type to D type, 2-wire system grounding resistance measurement: D type
Battery: AA alkaline dry cell x 4 pieces
Dimensions: W112 x H160 x D50mm
Weight: Approximately 350g (not including cell)
Accessories: Precision measuring probe set (red probe 20m x 1, Yellow probe 10m x 1, Green probe 5m x 1), T-type auxiliary grounding rod x 2, Simple type ground probe set (red x 1, Green x 1), Test rod flat (red x 1, Black x 1), Safety alligator clip (red alligator clip x 1, Black alligator clip x 1), Instruction manual: