After detecting the resistance change of the temperature measuring resistor, it is converted into an insulated instrumentation unified signal and output.
It has a built-in linearizer burnout function.
0.2 m gold plating is applied to the contact parts of the body and socket, providing high reliability and durability.
Specifications
measurement temperature range (degrees C) : 0 to 100
Supply power supply: AC100 to 240 V 50/60 Hz
Input signal: Pt 100
Output signal: DC4 to 20 mA
Allowable Voltage Range: 85 VAC to 264 V
Maximum Output Load: Current Output (DC)/4 to 20 mA Output 750 or less
Zero Point Adjustment Range: Approximately ± 5% of Span
Span Adjustment Range: Approx. ± 5% of Span
System Requirements: Temperature/-5 to + 55 ° C, Humidity/5 to 90 %RH (No condensation)
Mounting method: Wall mounting, DIN rail mounting common
Wiring Methods: M3.5 Screw Terminal Connections
external dimension : 29 x 86 x 125 mm (Including mounting screws and socket terminal block)
Weight: Body/120 g or Less, Socket Terminal Block/80 g or Less
*measurement temperature range can be specified from 0 to 50 ° C (Lowest) to 0 to 500 ° C (Best) in 50 ° C increments. Please contact us.