The DC input signal is compared with the two set points arbitrarily set by the front rotary switch, and the relay contact signal is output.
In this digital setting method, the rotary switch is used to set the set point in the range of 0 ~ 99% (1% steps).
Specifications
Output: Relay contact 2 (C contact)
Input Signal (mA): DC4 to 20
Supply power supply: AC100 to 240 V 50/60 Hz
Output Mode: H/Relay De-excitation (Input value < Set value)/Relay Excitation (Input value > Set value), L/Relay Excitation (Input value < Set value)/Relay De-excitation (Input value > Set value)
Allowable Voltage Range: 85 VAC to 264 V
Input Resistance: Current Input (DC)/4 to 20 mA (Standard) 250
Allowable Input Voltage: Current Input Type/DC 40 mA max. Continuous
Relay Contact: rating Load/5 A 125 VAC/5 A 30 VDC, Maximum Allowable Voltage/250 VAC/30 VDC, Maximum Allowable Current/5 A (N.O.)/3 A (N.C.)
Mounting method: Wall mounting, DIN rail mounting common
Wiring Methods: M3.5 Screw Terminal Connections
external dimension : 29 x 125 x 86 mm (Including mounting screws and socket terminal block)
Weight: Body/120 g or Less, Socket Terminal Block/80 g or Less